Products
Home > Products > Low Voltage Switchgear
Low voltage switch cabinet£¨MNS£©
Standard Specification

¡¾Overview and Model¡¿
In order to meet the needs of the development of power industry, MNS low-voltage extractive switchgear sets refer to the design of ABB series low-voltage switchgear abroad and improve the development of advanced low-voltage switchgear. MNS low-voltage switchgear adapts to the needs of various power supply and distribution, and can be widely used in power plants, substations, industrial and mining enterprises, buildings and hotels. Municipal construction and other low-voltage distribution systems.

¡¾Product characteristics ¡¿
1¡¢It can satisfy the requirements of various entry and exit schemes: up-in-up-out, up-in-down-out, down-in-up-out, down-in-down-out
2¡¢Compact design: smaller space to accommodate more functional units.
3¡¢Bus bar is protected by high strength flame retardant plastic functional board with high insulation strength, which has anti-fault arc performance and makes operation and maintenance safe and reliable.
4¡¢The mechanical interlocking mechanism of all kinds of drawers meets the requirements of the standard. It has three distinct positions: connection, test and separation. It is safe and reliable.
5¡¢Standard module design: can be composed of protection, operation, conversion, control, regulation, measurement, indication and other standard units, can be assembled arbitrarily according to the requirements.

¡¾Classification of Switchgear¡¿
Inlet cabinet: Installation of frame type low voltage circuit breaker, through the circuit breaker and copper buses of various sections (meeting current requirements)
The wire receives electricity and transfers it to the horizontal bus of the low voltage switchgear.
Matrix cabinet: Install frame type low-voltage circuit breaker, through the circuit breaker and copper buses of various sections (meeting current requirements) to realize the separation and transmission of electric energy between buses.
Feeder cabinet: Install frame type low voltage circuit breaker or plastic case type circuit breaker and branch buses and cables with various sections (meeting current requirements) to realize the transmission and distribution of electric energy in each circuit.
Capacitance Compensation Cabinet: Install self-healing (dry-type oil-free) low-voltage metal shunt capacitor, reactive power automatic compensator, knife fuse switch, contactor and other components and the corresponding secondary components to realize reactive power compensation of the system and improve the power factor of the system.
Motor control cabinet: Plastic case circuit breaker or micro switch, contactor, thermal relay and corresponding secondary components are installed to control mechanical and electrical equipment such as fan and wind valve.
¡¾Working conditions¡¿

1

ambient temperature

-10¡æ~+40¡æ   24-hour average temperature¡Ü35¡æ

2

relative humidity

The daily average is not more than 95%£¬The monthly average is not more than 90%£¨25¡æ£©

3

Saturated    vapor pressure

he daily average is not more than2.2¡Á10-3Mpa The monthly average is not more than1.8¡Á10-3Mpa

4

Altitude

¡Ü2000m

5

Earthquake intensity

¡Ü7degree£¨horizontal direction0.3g  vertical direction 0.15g£©

6

shock

F<10Hzʱ£¬Amplitude is 0.3mm 10<F<150Hzʱ£¬Acceleration is 0.1g

7

install

The inclination between vertical installation and vertical plane shall not exceed 5 degrees.

¡¾Main parameter ¡¿

1

Rated operating voltage£¨V£©

400

2

Rated insulation voltage£¨V£©

660

3

Rated frequency£¨Hz)

50

4

Rated working current£¨A)

Horizontal bus bar

630~5000

Vertical bus bar

 800~2000 £¨Feeding and MCC)

5

Rated short-term withstand current RMS 1 second £¨kA)

Horizontal bus bar

100kA

Vertical bus bar

85kA £¨Feeding and MCC)

6

Maximum rated short-term withstand current£¨kA£©

Horizontal bus bar

250kA

Vertical bus bar

196kA

7

Power frequency withstand voltage 1 minute £¨V)

2500

8

Shell protection grade

IP30 IP42 IP54

9

Electrical clearance

Inside drawer  10mm

Main circuit 20mm

 10

Creepage distance

Inside drawer  12mm

Main circuit   20mm

11

Isolation distance

It meets the requirements of JB4012-85 "Low Voltage Air Isolator, Switch, Isolator, Fuse and Combination Electrical Appliances", and has considered manufacturing tolerances and wear and tear

 

 

top
Product Catalog
Products